ShadowTrackr

Search the CVE vulnerability database

Look up vulnerabilities by software, product or CVE number.

← Back to results

CVE-2020-15795

A vulnerability has been identified in APOGEE PXC Compact (BACnet) (All versions < V3.5.5), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.20), APOGEE PXC Modular (BACnet) (All versions < V3.5.5), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.20), Nucleus NET (All versions < V5.2), Nucleus Source Code (Versions including affected DNS modules), TALON TC Compact (BACnet) (All versions < V3.5.5), TALON TC Modular (BACnet) (All versions < V3.5.5). The DNS domain name label parsing functionality does not properly validate the names in DNS-responses. The parsing of malformed responses could result in a write past the end of an allocated structure. An attacker with a privileged position in the network could leverage this vulnerability to execute code in the context of the current process or cause a denial-of-service condition.
8.1
CVSS
8.2
ShadowTrackr
NO
CISA KEV
-
NCSC.nl
CVSS v4.0 Metrics
Exploitability
Attack VectorNetwork
ComplexityHigh
RequirementsPresent
PrivilegesNone
User InteractionNone
Threat
Exploit MaturityPoC
Vulnerable System
ConfidentialityHigh
IntegrityHigh
AvailabilityHigh
Subsequent System
ConfidentialityNone
IntegrityNone
AvailabilityNone
Supplemental
SafetyNegligible
AutomatableYes
RecoveryAutomatic
Value DensityConcentrated
UrgencyMedium
Patch StatusUnavailable

Change Log
DateSourceChangesScore
2026-07-21cve.orginitial, patch: Unavailable8.2

Affected Software
VendorProductVersion
SiemensAPOGEE PXC Compact (BACnet)< 3.5.5
SiemensAPOGEE PXC Compact (P2 Ethernet)< 2.8.20
SiemensAPOGEE PXC Modular (BACnet)< 3.5.5
SiemensAPOGEE PXC Modular (P2 Ethernet)< 2.8.20
SiemensNucleus NET< 5.2
SiemensNucleus Source CodeVersions including affected DNS modules
siemensnucleus_net< 5.2
siemensnucleus_source_codeAll versions
SiemensTALON TC Compact (BACnet)< 3.5.5
SiemensTALON TC Modular (BACnet)< 3.5.5
Published: 2021-04-22